Shenzhen · Export in 8 Märkte +86 137 0631 0769  |  info@hsbyelectronics.com
Start / Produkte / Leistungsmessung / 1411-606-122 Model 606, Split Core Ct 1200:5 Ratio
1411-606-122 Model 606, Split Core Ct 1200:5 Ratio

1411-606-122 Model 606, Split Core Ct 1200:5 Ratio

1411-606-122 Model 606, Split Core Ct 1200:5 Ratio.

Angebot anfordern

Produktdetails

Main specifications and features Current ratio: 1200 A: 5 A (secondary rated 5 A) Accuracy level: ANSI metrological grade ± 1% (60 Hz) Rated load: 5 VA Working voltage once: 600 V AC (line to line) structure - Rectangular split iron core, can be opened and closed; Window dimensions are 1.30 inches high by 2.15 inches wide (approximately 33 mm by 55 mm) - Aluminum casing, built-in mounting plate, screw type secondary terminal Installation: directly clamped onto the busbar or cable without disconnecting the main circuit Certification: Compliant with IEEE/ANSI C57.13, BIL 10 kV Environment: -20...+60 ° C, IP20 Weight: Approximately 0.68 kg

Bestellinformationen

Nennen Sie Artikelnummer, Menge und Zieltermin. Wir bestätigen Bestand oder Lieferzeit, bieten bei Nichtverfügbarkeit eine Alternative und stellen eine Handelsrechnung mit HS-Code aus.

Ähnliche Produkte

Angebot oder schwer beschaffbare Position gesucht?

Senden Sie BOM oder Artikelnummern – Antwort innerhalb eines Werktags.

Kontakt